Locks and access
Exit devices and panic hardware: types and when code requires them
By the Div08 Consulting team · Updated
An exit device (often called a panic bar or crash bar) is door hardware that unlatches when someone pushes the bar on the egress side. The four main types are rim, surface vertical rod, concealed vertical rod and mortise. Codes require panic hardware on many assembly, educational and high-hazard doors, and fire-rated doors need devices labeled as fire exit hardware.
The four exit device types
Exit devices are covered by ANSI/BHMA A156.3. The type you pick is mostly decided by the opening: single door or pair, whether a mullion is acceptable, and whether the door is fire rated.
| Type | How it latches | Best fit | Watch for |
|---|---|---|---|
| Rim | One latch at the edge, into a surface strike on the frame | Single doors; pairs with a mullion | Pairs need a mullion or a second device type |
| Surface vertical rod (SVR) | Rods on the door face latch at the head and floor | Pairs without a mullion | Exposed rods; the bottom latch takes abuse |
| Concealed vertical rod (CVR) | Rods inside the door latch at the head and floor (or head only) | Pairs where a clean look matters | Needs factory door prep; harder to service |
| Mortise | A mortise lock body in the door edge | Single doors with heavy traffic, high security | Requires mortise prep in the door |
Many manufacturers offer vertical rod devices less bottom rod (LBR), which latch only at the head. That removes the floor strike that collects debris and gets damaged by carts, but whether LBR is allowed on a fire-rated pair depends on the device listing and the door manufacturer's label.
Panic hardware vs fire exit hardware
Panic hardware is listed for life safety: it lets people get out. Fire exit hardware is panic hardware that is also labeled for use on fire doors, so it keeps the door positively latched during a fire.
The practical difference shows up in options. Mechanical dogging (holding the latch retracted so the door works push/pull) is common on panic hardware but is not permitted on fire exit hardware, because a fire door must latch every time it closes. If an owner wants push/pull operation on a fire door, the usual answer is electric latch retraction tied to the fire alarm so the latch releases back to latching when the alarm activates.
Spec tip
when a pair is fire rated, confirm the exit devices, the door, the frame and any astragal are all compatible under the door manufacturer's label before the hardware set is finalized. A device that is fire rated on its own can still be wrong for that particular door.
When code requires panic hardware
Under the IBC, panic or fire exit hardware is generally required on egress doors that are latched or locked in these situations:
- Assembly (Group A) and educational (Group E) occupancies where the occupant load reaches the threshold in the adopted code (50 or more in recent IBC editions).
- High-hazard (Group H) occupancies.
- Doors from rooms containing large electrical equipment (recent IBC and NFPA 70 editions set the trigger at equipment rated 800 amperes or more; older editions used 1,200 amperes).
NFPA 101 has its own occupancy rules, and some jurisdictions amend both codes. Always check the code edition the AHJ has adopted and the life safety plan for the project rather than relying on a general rule.
IBC also sets performance requirements for the device itself: the actuating portion must extend across at least half the door leaf width, and the force needed to release the latch is limited (15 pounds in recent editions). Hardware on accessible routes must also meet the 34 to 48 inch mounting height range covered in our ADA door requirements guide.
Outside trim and functions
On the pull side, an exit device can have no trim at all (exit only), a pull, a lever, or a knob, and the trim sets the function. Common choices:
- Exit only: no outside hardware. Typical for stair and back-of-house egress doors.
- Night latch: outside key retracts the latch momentarily.
- Passage: outside lever always works.
- Classroom style: a key locks or unlocks the outside lever.
- Storeroom style: the outside lever is always locked, and the key retracts the latch momentarily.
Do not add a separate deadbolt or surface bolt to a door with panic hardware. The code generally allows no lock or latch on these doors other than the panic or fire exit hardware itself, because an extra lock defeats the single egress motion. The exceptions are narrow (for example, certain electrical locking systems and a key-operated lock on the main entrance of some assembly occupancies under specific conditions), so check the adopted code before relying on one.
Electrified options
Exit devices come with electrified trim (outside lever locked or unlocked by access control), electric latch retraction, request-to-exit switches, and latch or dogging monitoring. Power gets to the device through an electric hinge, a power transfer or a door loop, which belongs in the hardware set along with the power supply. See electric strike vs maglock for how fail-safe and fail-secure apply here.
Spec tip
write every electrified opening up with a wiring diagram reference and call out who supplies the power supply and the access control interface. Missing coordination between Division 08 and Division 28 is one of the most common reasons an opening is wrong at turnover.
Frequently asked questions
Is a panic bar the same as an exit device?
Yes. Panic bar, crash bar and push bar are informal names for an exit device. The listing on the device decides whether it is panic hardware or fire exit hardware.
Can you dog down an exit device on a fire door?
Not mechanically. Fire exit hardware cannot have mechanical dogging. Electric latch retraction that releases on fire alarm is the usual way to get push/pull operation on a fire door.
Do exit devices need to meet ADA?
On accessible routes the operable part must be within the ADA mounting height range and operate without tight grasping or twisting. Push-bar devices generally meet the operation requirement.
When is panic hardware required?
Generally on latched or locked egress doors in assembly and educational occupancies above the code's occupant load threshold, in high-hazard occupancies, and at certain electrical rooms. Check the adopted code and the AHJ.
General guidance only. Code requirements depend on the edition your jurisdiction has adopted and on the listing of each fire-rated assembly; confirm with the authority having jurisdiction. Published by Div08 Consulting (John Voll, owner).